SCF122-DI

Controllers for Diesel Fire Pumps according to EN 12845 and UNE 2300

SCF122-DI are designed to meet and exceed the requirements of the EN 12845 and UNE 23500 standard; They are high specification instruments that apply the most advanced technology. They offer unrivalled features such as communications,  configurations, versatility and robustness.

SCF122-DI controllers govern the starting and stopping process of the Diesel Fire Pumps and protect them through the action of the alarms both connected and generated by the controller itself; they visualise the most relevant values and information, also manage the communication with the operator and with both the contour elements and the remote manned centre

MAIN FEATURES: SCF122-DI

Diesel engine Fire Pumps controllers: EN 12845 and UNE 2300

  • Nº STANDARDS & TECHNICAL RULES
    1 Standard EN 12845 Ed.2015
    2 Standard UNE 23500 Ed.2012
    3 Standard UNI 10779 Ed. 2014
    4 Standard IEC 61439-1 Ed. 2011 Low-voltage switchgear and controlgear assemblies
    5 Tech. Rule CEPREVEN R.T.1-ROC Ed.2004
    6 Tech. Rule CEPREVEN R.T.2-ABA Ed.2006
  • Nº RANGE OF PRODUCTS (according to the type plate)
    1 Nominal supply voltage 230 V AC
    2 Nominal frequency 50Hz / 60Hz.

     

    RANGE OF PANELS ACCORDING TO BATTERY CHARGERS  SCF122-DI 12070 SCF122-DI 12100 SCF122-DI 24035 SCF122-DI 24050
    Nominal Voltage 12 V DC 12 V DC 24 V DC 24 V DC
    Rated Amp 7 A 10 A 3,5 A 5 A
    DIN Power 96,6 W 138,0W 96,6 W 138,0 W
    Capacity of the batteries (C10) 200 Ah 285 Ah 100 Ah 142 Ah
  • Nº CONSTRUCTIVE FEATURES
    1 Enclosure Ingress protection rating: IP65
    2 Protection against impacts degree: IK10 except PLC IGNIMATIC D122
    3 Fireproof degree: The fire is extinguished in <30s with dripping
    4 Display LCD 4 lines / 20 characters
    5 Cabling Free of halogens
    6 Fire resistance: RZ1 according to EN50200 (Max: 830º / 90min)
    7 Working temperatures From -5ºC to 50ºC
  • Nº MEASURING INSTRUMENTS IN THE DISPLAY
    1 Batteries 2 Voltmeter: Battery voltage
    2 2 Ammeter: Battery charging Amp
    4 1 Battery equalization timer
    5 Engine 1 Fuel tank level meter
    6 1 Oil pressure gauge (sensor not included)
    7 1 Engine temperature thermometer (sensor not included)
    8 1 Engine speed meter (sensor not included)
  • Nº PUMP & SYSTEM PROTECTION
    1 System not in autamatic mode
    2 Mains failure
    3 Engine over-speed
    4 Low oil pressure
    5 High engine temperature
    6 Low fuel level
    7 Battery A low voltage
    8 Battery B low voltage
    9 Loss of charger A protection
    10 Loss of charger B protection
    11 Heater overload tripped
    12 Bendix voltage fail
    13 Fail to start
    14 Discharge pressure fail
    15 Low reservoir tank
    16 Low priming tank
    17 Pick-up fault
  • 1 RS485 port (Optional) IGNIMATIC D122 controller configuration
    2 PC monitoring: Pump and installation general condition
    3 Ethernet port (Optional) IGNIMATIC D122 controller configuration
    4 PC monitoring: Pump and installation general condition
    5 Voltage free contacts :
    up to 30 V DC / 0,3 A
    Power not available
    6 Automatic mode Off
    7 Fail to start / not discharge pressure
    8 Grouped alarms
    9 Pump on demand
    10 Pump running with pressure
  • Nº LANGUAGES / OTHER FEATURES
    1 ENGLISH/ ESPAÑOL / ITALIANO / FRANÇAIS / PORTUGUES
    2 Engine heating management via temperature reading probe
    3 Engine hours
    4 Engine coolant circuit management
    5 Buzzer: 80dB
    6 Event historical: Last 47 events
SVE
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.