FIRE FIGHTING

SCF830-D-AS

DISCONTINUED
AS2941 Diesel Fire pump Controller

Controllers for Diesel Fire Pumps according to AS 2941 and AS 3000

SCF830-D-AS are designed to meet and exceed the requirements of the AS 2941 standard; They are high specification instruments that apply the most advanced technology. They offer unrivalled features such as communications,  configurations, versatility and robustness.

SCF830-D-AS controllers govern the starting and stopping process of the Diesel Fire Pumps and protect them through the action of the alarms both connected and generated by the controller itself; they visualise the most relevant values and information, also manage the communication with the operator and with both the contour elements and the remote manned centre.

MAIN FEATURES: SCF830-D-AS

Diesel Fire Pumps controllers: AS 2941

  • STANDARDS & TECHNICAL RULES
    1 Standard AS 2914 Ed.2013
    2 Standard AS/NZS 3000 Ed.2007
  • RANGE OF PRODUCTS (according to the type plate)
    1 Nominal supply voltage 230 V AC
    2 Nominal frequency 50Hz / 60Hz.

     

    RANGE OF PANELS ACCORDING TO BATTERY CHARGERS SCF122-DI 12070 SCF122-DI 12100 SCF122-DI 24035 SCF122-DI 24050
    Nominal Voltage 12 V DC 12 V DC 24 V DC 24 V DC
    Rated Amp 7 A 10 A 3,5 A 5 A
    DIN Power 96,6 W 138,0W 96,6 W 138,0 W
    Capacity of the batteries (C10) 200 Ah 285 Ah 100 Ah 142 Ah
  • CONSTRUCTIVE FEATURES
    1 Enclosure Ingress protection rating: IP65
    2 Protection against impacts degree: IK10 except PLC SAF830-D-AS
    3 Fireproof degree: The fire is extinguished in <30s with dripping
    4 Display Graphic / Transflective
    5 Cabling Free of halogens
    6 Fire resistance: RZ1 according to EN50200 (Max: 830º / 90min)
    7 Working temperatures From -5ºC to 50ºC
  • MEASURING INSTRUMENTS IN THE DISPLAY
    1 Batteries 2 Voltmeter: START & MONITOR Batteries voltage
    2 2 Ammeter: START & MONITOR Batteries charging Amps
    3 1 Ammeter: Engine auxiliary alternator Amps
    4 1 Battery equalization timer
    5 Engine 1 Fuel tank level meter
    6 1 Oil pressure gauge (sensor not included)
    7 1 Engine wáter thermometer (sensor not included)
    8 1 Engine oil thermometer (sensor not included)
    9 1 Engine speed meter (sensor not included)
    10 System 1 System pressure meter (sensor not included)
    11 1 Flow meter ( manual introduction / 4⁄20mA sender not included)
    12 1 Voltmenter V AC  supply voltaje
    13 1 Frequencymeter: Mains supply frequency
  • PUMP & SYSTEM PROTECTION
    1 MAINS FAILURE
    2 OVER SPEED
    3 LOW OIL PRESSURE
    4 ENGINE HIGH WATER TEMPERATURE
    5 LOW FUEL LEVEL
    6 LOW BATTERY START VOLTAGE
    7 LOW BATTERY MONITOR VOLTAGE
    8 CHARGER START FAULT
    9 CHARGER MONITOR FAULT
    10 HEATER PROTECTION TRIPPED
    11 CRANK ENGINE VOLTAGE FAIL
    12 FAILED TO START
    13 LOW DISCHARGE PRESSURE
    14 LOW RESERVOIR TANK
    15 LOW PRIMING TANK
    16 SPEED SIGNAL FAULT
    17 PRESSURE SWITCH SHORT-CIRCUIT
    18 PRESSURE SWITCH OPEN-CIRCUIT
    19 MAINS FREQUENCY FAIL
    20 COMMUNICATION
    30 CRANKING LEVERS FAULT
    31 ENGINE LOW WATER  TEMPERATURE
    32 DC VOLTAGE FAIL
    33 HIGH START BATTERY  VOLTAGE
    34 HIGH MONITOR BATTERY  VOLTAGE
    35 START BATTERY  DEFECTIVE
    36 MONITOR BATTERY  DEFECTIVE
    37 WATER PRESSURE SENSOR FAULT
  • 1 Device: USB connector type B Communication SAF830-D<—> PC
    2 Host: USB connector type Communication SAF830-D<—> Pendrive (external memory)
    3 Ethernet port (TCP/IP) PC monitoring: Pump and installation general condition
    4 RS 485 port (Optional) PC monitoring: Pump and installation general condition
    5 Voltage free contacts :
    up to 30 V DC / 0,5 A
     Power  fail
    6 Pump running with pressure
    7 Pump running with pressure
    8 Pump on demand
    9 Failed to start / Discharge pressure fail
    10 Not in auto mode
    11 Grouped alarms / Control fail
    12 Grouped alarms / Control fail
  •  OTHER FEATURES
    1 Attached solenoid box. ( Cranking levers) . Connection fault alarm
    2 Monitored pressure switch lines: Short circuit / open circuit alarm
    3 Crank isolate cover protected by padlock
    4 Pump demand by pressure transducer analog reading of system pressure
    5 Current date and time (RTC with independent battery)
    6 500 last events log (starts, alarms, …)
    7 16,000 latest records of system pressure variation
    8 50 pressure / Flow pump test récords
    9 Calibration of analog measurements: Pressure / Voltage / Temperature …
    10 Digital and analog inputs and outputs checking of on the display
    11 Accumulate engine operations hours and minutes
    12 Engine cooling circuit management
    13 Engine heating resistence management